Physical data

Outdoor unit RAV-SM2244AT8-E / AT7 RAV-SM2804AT8-E / AT7
8 HP 10 HP
Air Flow m3/h - l/s 8000 - 2222 9000 - 2500
Sound pressure level dB(A) C 56 57
Sound power level dB(A) C 72 74
Operating range °C C -15 / 46 -15 / 46
Sound pressure level dB(A) H 57 58
Sound power level dB(A) H 74 75
Operating range °C H -20 / 15 -20 / 15
Dimensions (HxWxD) mm 1540 x 900 x 320 1540 x 900 x 320
Weight kg 134 134
Compressor type DC Twin Rotary DC Twin Rotary
Flare connections
Gas in 1 1/8 1 1/8
Liquid in 1/2 1/2
Minimum pipe length m 7,5 7,5
Maximum pipe length m 70 70
Maximum height difference m 30 30
Chargeless pipe length m 30 30
Power supply V-ph-Hz 380/415-3N-50 / 380-3N-60Hz 380/415-3N-50 / 380-3N-60Hz
C = cooling mode
H = heating mode
Electrical Data for 60Hz Model could vary slightly, please refer to technical databook for specifics details.
The specification may be subject to change without notice for purpose of improvement.